CVE-2024-50954High
Share link
Anyone with the link can open this vulnerability.
The XINJE XL5E-16T and XD5E-24R-E programmable logic controllers V3.5.3b-V3.7.2a have a vulnerability in handling Modbus messages. When a T…
CVSS
7.5
High
EPSS
0.00
p53
Published
2024-01-01
Updated
2024-01-01
Description
The XINJE XL5E-16T and XD5E-24R-E programmable logic controllers V3.5.3b-V3.7.2a have a vulnerability in handling Modbus messages. When a TCP connection is established with the above series of controllers within a local area network (LAN), sending a specific Modbus message to the controller can cause the PLC to crash, interrupting the normal operation of the programs running in the PLC. This results in the ERR indicator light turning on and the RUN indicator light turning off.
Tags · CWE
Pre-auth
CWE-703
CWE-703PillarIncomplete
Improper Check or Handling of Exceptional Conditions
The product does not properly anticipate or handle exceptional conditions that rarely occur during normal operation of the product.
https://cwe.mitre.org/data/definitions/703.html →Open in CWE collection →CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Timeline
2024-01-01
Published
2024-01-01
Updated
CVSS 3.1 breakdown
Attack Vector
AV: N
Network (N)
Attack Complexity
AC: L
Low (L)
Privileges Required
PR: N
None (N)
User Interaction
UI: N
None (N)
Scope
S: U
Unchanged (U)
Confidentiality Impact
C: N
None (N)
Integrity Impact
I: N
None (N)
Availability Impact
A: H
High (H)
Exploit indicators
EPSS
0.003 · p53
Known exploited (KEV)
No
Known exploits — Сканер-ВС
No Сканер-ВС checks registered for this vulnerability yet.