Vulnerabilities
32
Known exploited
0
Max CVSS
10
Top EPSS
0.08978

Severity breakdown

Critical
10
High
17
Medium
5
Low
0

Affected version ranges

< 3.20< 3.30< 3.40< 3.50< 3.60
Also matched as (raw): modicon_m340_bmxp342020_firmware

Top vulnerabilities

CVE-2014-0754Directory traversal vulnerability in SchneiderWEB on Schneider Electric Modicon PLC Ethernet modules 140CPU65x Exec before 5.5, 140NOC78x Exec before 1.62, 140NOE77x Exec before 6.2, BMXNOC0401 before 2.05, BMXNOE0100 before 2.9, BMXNOE0110x Exec before 6.0, TSXETC101 Exec before 2.04, TSXETY4103x Exec before 5.7, TSXETY5103x Exec before 5.9, TSXP57x ETYPort Exec before 5.7, and TSXP57x Ethernet Copro Exec before 5.5 allows remote attackers to visit arbitrary resources via a crafted HTTP request.
CVE-2022-45789A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions)
CVE-2022-45788A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions)
CVE-2022-37300A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbers BMXP34*) (V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*) (V3.20 and prior).
CVE-2020-7540A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause unauthenticated command execution in the controller when sending special HTTP requests.
CVE-2018-7761A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution.
CVE-2018-7760An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization.
CVE-2018-7242Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks.
CVE-2018-7241Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules.
CVE-2021-22779Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.
CVE-2020-7534A CWE-352: Cross-Site Request Forgery (CSRF) vulnerability exists on the web server used, that could cause a leak of sensitive data or unauthorized actions on the web server during the time the user is logged in. Affected Products: Modicon M340 CPUs: BMXP34 (All Versions), Modicon Quantum CPUs with integrated Ethernet (Copro): 140CPU65 (All Versions), Modicon Premium CPUs with integrated Ethernet (Copro): TSXP57 (All Versions), Modicon M340 ethernet modules: (BMXNOC0401, BMXNOE01, BMXNOR0200H) (All Versions), Modicon Quantum and Premium factory cast communication modules: (140NOE77111, 140NOC78*00, TSXETY5103, TSXETY4103) (All Versions)
CVE-2023-6408 CWE-924: Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability exists that could cause a denial of service and loss of confidentiality, integrity of controllers when conducting a Man in the Middle attack.
CVE-2022-0222A CWE-269: Improper Privilege Management vulnerability exists that could cause a denial of service of the Ethernet communication of the controller when sending a specific request over SNMP. Affected products: Modicon M340 CPUs(BMXP34* versions prior to V3.40), Modicon M340 X80 Ethernet Communication modules:BMXNOE0100 (H), BMXNOE0110 (H), BMXNOR0200H RTU(BMXNOE* all versions)(BMXNOR* versions prior to v1.7 IR24)
CVE-2021-22788A CWE-787: Out-of-bounds Write vulnerability exists that could cause denial of service when an attacker sends a specially crafted HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum Processors with Integrated Ethernet (Copro): 140CPU65xxxxx (All Versions), Modicon Quantum Communication Modules: 140NOE771x1, 140NOC78x00, 140NOC77101 (All Versions), Modicon Premium Communication Modules: TSXETY4103, TSXETY5103 (All Versions)
CVE-2021-22787A CWE-20: Improper Input Validation vulnerability exists that could cause denial of service of the device when an attacker sends a specially crafted HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum Processors with Integrated Ethernet (Copro): 140CPU65xxxxx (All Versions), Modicon Quantum Communication Modules: 140NOE771x1, 140NOC78x00, 140NOC77101 (All Versions), Modicon Premium Communication Modules: TSXETY4103, TSXETY5103 (All Versions)
CVE-2021-22786A CWE-200: Information Exposure vulnerability exists that could cause the exposure of sensitive information stored on the memory of the controller when communicating over the Modbus TCP protocol. Affected Products: Modicon M340 CPU (part numbers BMXP34*) (Versions prior to V3.30), Modicon M580 CPU (part numbers BMEP* and BMEH*) (Versions prior to SV3.20), Modicon MC80 (BMKC80) (Versions prior to V1.6), Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) (All Versions), Modicon Momentum MDI (171CBU*) (Versions prior to V2.3), Legacy Modicon Quantum (All Versions)
CVE-2021-22785A CWE-200: Information Exposure vulnerability exists that could cause sensitive information of files located in the web root directory to leak when an attacker sends a HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum Processors with Integrated Ethernet (Copro): 140CPU65xxxxx (All Versions), Modicon Quantum Communication Modules: 140NOE771x1, 140NOC78x00, 140NOC77101 (All Versions), Modicon Premium Communication Modules: TSXETY4103, TSXETY5103 (All Versions)
CVE-2020-7543A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
CVE-2020-7542A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
CVE-2020-7539A CWE-754 Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause a denial of service vulnerability when a specially crafted packet is sent to the controller over HTTP.
CVE-2020-7537A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
CVE-2020-7536A CWE-754:Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M340 CPUs (BMXP34* versions prior to V3.30) Modicon M340 Communication Ethernet modules (BMXNOE0100 (H) versions prior to V3.4 BMXNOE0110 (H) versions prior to V6.6 BMXNOR0200H all versions), that could cause the device to be unreachable when modifying network parameters over SNMP.
CVE-2020-7535A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP.
CVE-2018-7762A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow.
CVE-2018-7759A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. The buffer overflow vulnerability is caused by the length of the source string specified (instead of the buffer size) as the number of bytes to be copied.